ACT-HPC Heat Pipe Coolers

Home  |  Enclosure Cooling  |  ACT-HPC Heat Pipe Coolers

SEALED ENCLOSURE COOLING FROM 15 WATTS/°C TO 80 WATTS/°C

Off the shelf, passive sealed enclosure coolers consist of a heat pipe heat exchanger core with advanced fin features for enhanced heat transfer performance.

  • Optimized for high performance/volume ratios
    • Best performance when installed vertically through the top wall (roof) of the enclosure
    • Performance may decrease slightly when installed horizontally through a sidewall of the enclosure with the mounting wedge accessory.
  • Easy to install
  • Smaller opening footprint on the enclosure wall than the HSC-series
  • Dual axial ball bearing fans for years of maintenance-free operation
  • PayPal Acceptance Mark1-Year Warranty (see ACT’s Terms and Conditions)
  • Order through our experienced sales staff or buy online through ACT’s online store

ACT-HPC PRODUCTS

*Scroll right to view table

Part Number Thermal Conductance Watts
/
°C
Thermal Capacity Watts @ 20°C T Weight*
lbs. (kg)
Height Width
Depth
Insertion Depth

Mounting Plate
ACT-HPC-15 15.0 300 7.0 (3.2) 11.30″
287.0mm
5.43″
137.9mm
5.36″
136.1mm
5.63″
143.0mm
6.75″ x 6.75″
(171.5x 171.5)
ACT-HPC-40          40.0 800 17.0 (7.7) 15.0″
381.0mm
7.94″
201.4mm
7.90″
200.7mm
7.40″
189.7mm
10.0″ x 10.0″
(254.0mm x 254.0mm)
ACT-HPC-50 50.0 1,000 27.0 (12.2) 22.0″
558.8mm
7.94″
201.4mm
7.90″
200.7mm
10.90″
278.6mm
10.0″ x 10.0″
(254.0mm x 254.0mm)
ACT-HPC-80 80.0 1,600 37.0 (16.8) 15.0″
381.0mm
15.15″
391.9mm
7.90″
200.7mm
7.40″
189.7mm
10.0″ x 17.5″
(254.0mm x 444.5mm)

Notes: *Weight for NEMA 4X models will be slightly greater.

ACT-HPC MAXIMUM CURRENT DRAW BY MODEL

*Scroll right to view table

Model ACT-HPC-15 ACT-HPC-40 ACT-HPC-50 ACT-HPC-80
NEMA Rating Voltage Maximum Operation Current
in Amps
Maximum Operation Current in Amps Maximum Operation Current in Amps Maximum Operation Current
in Amps
4, 4X, 3R (12) 12VDC 1.80 3.60 (3.90) 3.60 (3.90) 7.20 (7.80)
4, 4X, 3R (12) 24VDC 0.92 1.64 (1.66) 1.64 (1.66) 3.28 (3.32)
4, 4X, 3R (12) 48VDC 0.52 0.88 (0.92) 0.88 (0.92) 1.76 (1.84)
4, 4X, 3R, 12 115VAC 0.60 0.72 0.72 1.44
4, 4X, 3R, 12 230VAC 0.28 0.38 0.38 0.76

ACT-HPC SERIES FEATURES AND OPTIONS

*Scroll right to view table

Environment Indoor or Outdoor Use
Electrical Configuration 115VAC units arrive with 6ft. long 3-pronged plug
230VAC, 12VDC, 24VDC and 48VDC  units arrive with bare lead wires
UL Listing &
UL Recognition
The 115VAC units received a UL listing mark
All other versions are UL Rated/UL Recognized (230VAC, 12VDC, 24VDC, and 48VDC)
NEMA Options 12, 3R, 4 and 4X, UL50E Certified
Fans UL Listed 4.0” and 6.0” dual ball bearing type axial fans (dry & wet locations)
Mounting Plate 304 stainless steel
HPC Housing Powder-coated aluminum, Optional: stainless steel
Mounting Options Top (best performance); side, front or back (de-rated performance)
Operating Temperature Range 14°F (-10°C) to 140°F (+60°C)
Expected Fan Life >100,000 Hours at 77°F (+25°C)
Accessories Rain guards; removable filters (only needed for excessively rugged or dirty environments, i.e. desert or coal mines)

 

Top