ACT-HPC Heat Pipe Coolers

Home  |  Enclosure Cooling  |  ACT-HPC Heat Pipe Coolers

HPC Group Photo 7-12

SEALED ENCLOSURE COOLING FROM 15 WATTS/°C TO 80 WATTS/°C

    • Passive sealed enclosure coolers consisting of a heat pipe heat exchanger core with
      advanced fin features for enhanced heat transfer performance
    • Optimized for high performance/volume ratios
    • Best performance when installed vertically through the top wall (roof) of the enclosure
    • Performance may decrease slightly when installed horizontally through a side wall of the enclosure. Please use the Online Selection Tool or contact ACT to determine the HPC’s performance at a horizontal orientation
    • Smaller opening footprint on the enclosure wall than the HSC-series
    • Dual axial ball bearing fans for years of maintenance free operation
    • Easy to install
    • 1-Year Warranty (see ACT’s Terms and Conditions)

ACT-HPC PRODUCTS

Part Number Thermal Conductance Watts/°C Thermal Capacity Watts @20°C ΔT Weight (lbs) H (in”) W (in”) D (in”) Base Price
ACT-HPC-15 15 300 7 11.3 5.145 5.0 $830
ACT-HPC-40 40 800 17 15 7.645 7.5 $995
ACT-HPC-50 50 1000 27 22 7.65 7.5 $1,495
ACT-HPC-80 80 1600 37 15 15.15 7.5 $1,950

HPC Series BarEnvironment…………………………………………….………………. Indoor or Outdoor Use

Electrical Configuration…………………………………………… 115VAC, 230VAC, 12VDC, 24VDC and 48VDC
………………………………………………………………………………….  – 115 VAC units arrive with 6ft. long 3-pronged plug
…………………………………………………………………………………..  – DC units arrive with 3-conductor, 6.0′ flying lead wires

NEMA Options…………………………………………………………. 12, 3R, 4 and 4X, UL50E Certified

Fans…………………………………………………………………………  UL Listed 6.0” ball bearing type axial fans
………………………………………………………………………………….  (dry & wet locations)

UL Listing & UL Recognition…………………………………. The 115VAC units received a UL listing mark. All other voltage
…………………………………………………………………………………. versions (230VAC, 12VDC, 24VDC, and 48VDC) are
…………………………………………………………………………………. UR Rated/UL  Recognized

Mounting Plate………………………………………………………… 304 Stainless Steel

Operating Temperature…………………………………………… 14°F (-10°C) to 140°F (+60°C)

HPC Housing…………………………………………………………… Powder coated aluminum, Optional: stainless steel

Enclosure Mounting Options…………………………………. Top (best performance), side, front or back
……………………………………………………………………(derated performance), contact ACT or use our Online Selection Tool

Other Options………………………………………………………….. Rain guards and removable filters

 

HPC Performance Curve

HPC 80RT

The ACT-HPC enclosure coolers are available in NEMA 3R. The 3R rain guards can be installed at anytime.

Part Number Insertion Depth (in”) Mounting Plate (in”)
ACT-HPC-15 5.6 6.75 x 6.75
ACT-HPC-40 7.4 10.0 x 10.0
ACT-HPC-50 10.9 10.0 x 10.0
ACT-HPC-80 7.4 10.0 x 17.5

 

 

 

 

 

 